Circuit Breaker Sizing Calculator

Select the right protective device the way BS 7671 demands it: the breaker must carry the design current, must not exceed what the cable can withstand under its real installation conditions (Ib ≤ In ≤ Iz), must ride through the load’s starting current without nuisance tripping, and must provide the right earth-leakage protection for the circuit type. Enter the load, its inrush, and the cable it protects, and the calculator returns a recommended MCB, MCCB or RCBO rating, the pole configuration, and trip-curve guidance with reasons.

The cable itself should be sized first — use the Cable Sizing and Voltage Drop Calculator, then verify the breaker here.

SheetCALC-06
TitleCircuit Breaker Sizing Calculator
BasisIb ≤ In ≤ Iz · IEC 60898
Rev2026-07
1 · Load
Sets sensible defaults for power factor, trip curve and RCD guidance.
2 · Cable + Installation Conditions
The cable this breaker must protect. Not sized yet? Use the Cable Sizing Calculator first.
Guides the breaking-capacity (Icn/Icu) recommendation.

Protective device selection CALC-06 · REV 2026-07

Design current, Ib
Cable capacity, tabulated Iz
Derating, Ca × Cg
Cable capacity after derating, Iz
Recommended device
Coordination check, Ib ≤ In ≤ Iz
Pole configuration
Trip curve
Estimated inrush
RCD / earth-leakage protection
Breaking capacity

Guidance tool only. The selection assumes BS EN 60898 / 61009 / 60947 devices and typical cable data; the full design must also verify earth-fault loop impedance (Zs) against the chosen curve, discrimination with upstream devices, and short-circuit energy let-through — work for a registered engineer.

How this calculator works

  1. Design current. Entered directly or computed from kW, voltage, phase and power factor, exactly as in the cable calculator.
  2. Coordination, Ib ≤ In ≤ Iz. The breaker rating In must sit between the design current and the cable’s current-carrying capacity after derating for ambient temperature and grouping (Tables 4B1 and 4C1). The companion condition I2 ≤ 1.45 Iz is met automatically by BS EN 60898 and 61009 devices once In ≤ Iz. If no standard rating fits between the two, the cable is the problem — the calculator says so and suggests the minimum compliant size.
  3. Trip curve. Curves B, C and D trip magnetically at 3–5, 5–10 and 10–20 times In respectively. To avoid nuisance tripping, the starting current should sit below In times the curve’s lower threshold; the calculator computes the inrush-to-rating ratio and selects accordingly, never going below the practical minimum for the load type. Inrush beyond 10× points to an MCCB with adjustable settings or a soft starter.
  4. Poles and RCD. Single-phase final circuits use 1P (or 1P+N RCBO); bathroom and EV circuits get double-pole isolation; three-phase motors take 3P and mixed three-phase loads 3P+N. Thirty-milliamp additional protection follows BS 7671: sockets up to 32 A (Reg 411.3.3), bathrooms (Section 701), EV charging with Type A + 6 mA DC detection (Section 722), and domestic lighting in new work (Reg 411.3.4). Feeders instead take time-delayed upstream earth-leakage for discrimination.
  5. Breaking capacity. Guidance scales from 6 kA (typical domestic, BS EN 60898) through 10 kA commercial boards to verified fault-level MCCB selection near transformers (BS EN 60947-2).

Assumptions and limits

  • Cable capacities use the same typical PVC multicore tables as the cable calculator; XLPE and single-core installations need manufacturer data.
  • Earth-fault loop impedance (Zs) verification per curve, discrimination studies and let-through energy checks are outside this tool and mandatory in a full design.

Building a full distribution board schedule? Our consultancy services and design document library cover it, or learn the method in a training program.

Share This